🚀 Motor Selection Calculator

Compute required motor power from load and efficiency.

📐 计算公式
电机选型(由负载功率正推,非由扭矩反推):所需电机功率 P = 负载功率 P_load ÷ (η÷100)(kW,η 为传动效率%);计算转矩 T = 9550×P ÷ n(N·m,n 为转速 rpm);推荐标准功率取 IEC 表中首个 ≥P 的档位(0.75~630kW 共 30 档),额定转矩 = 9550×标准功率 ÷ n;若所需功率超过 630kW 则只输出所需功率与超系列告警,不给出推荐档位与额定转矩。校验:三项非空守卫,任一非数、n≤0、η≤0 或 η>100 报「请输入有效参数(转速、效率需大于 0,效率不超过 100%)」。判据:功率裕量 = (标准功率−P)÷P×100%,<10% 提示裕量偏小建议放大一档,否则裕量合适。
根据负载功率、转速与传动效率计算所需电机功率,匹配 IEC 标准功率等级并核算转矩
💡 所需电机功率 P = P_load / η;转矩 T = 9550 × P / n (N·m);按 IEC 标准功率等级向上匹配。

Formula & Standard References

Item Formula / Note Source / Standard
Power relationship motor output power equals torque times angular speed derived from rpm IEC 60034-1:2017, rotating electrical machines
Duty type continuous and short time duty need different sizing margins IEC 60034-1:2017, rotating electrical machines
Efficiency and rise efficiency class and permissible temperature rise bound usable power IEC 60034-30-1:2014, efficiency classes
⚠️ 注意事项
  • 传动效率参考:直联≈99%、联轴器≈97~99%、皮带≈95%、齿轮减速≈95~98%、蜗轮≈60~80%
  • 选型功率应略大于计算功率并留 10~20% 裕量,避免长期满载或过载
  • 频繁起动、冲击负载场合应选 YZ 等高起动转矩系列或放大一档
  • 按 Enter 快速计算,Ctrl/Cmd + Enter 复制结果;纯前端运行,数据不上传