⚡ Conductor Ampacity Selection

From current, ambient temperature, laying method and line length, selects a conductor cross-section and verifies the voltage drop.

📐 計算公式
單程電阻 R = ρ·L/1000;電壓降 ΔU = 2·I·R(來回雙線);壓降% = ΔU/V × 100%;線損 P = 2·I²·R(W)
導線載流選型:基於電流、環境溫度與敷設方式,按導線載流量修正曲線選擇線徑,校核電壓降與溫升,用於配電線路設計。
💡 按校正載流量選截面;壓降 ΔU=2×I×R×L,銅電阻率 0.0184 Ω·mm²/m

Formula & Standard References

ItemFormulaSource / Standard
One-way R One-way R = ρ × L / 1000 Voltage drop
Drop Drop ΔU = 2 × I × R (round trip) Voltage drop
Drop% / loss Drop% = ΔU / V × 100; loss P = 2 × I² × R (W) Voltage drop
⚠️ 注意事項
  • 壓降一般不超過 5%(照明 3%、動力 5%)
  • 穿管敷設降容 15%,線槽敷設降容 22%
  • 長距離輸電需校驗壓降,可能需放大截面
  • 本工具純前端執行,資料不會上傳到伺服器

📐 Material Constants

Basis for the resistivity and derating values used here, for verification and citation

Constant Value Unit Source
Volume resistivity of annealed copper (20 ℃) 1.7241e-8 (= 0.017241) Ω·m (Ω·mm²/m) IEC 60028 (IACS 100%)
Volume resistivity of hard-drawn aluminium (20 ℃) 2.8264e-8 (= 0.028264) Ω·m (Ω·mm²/m) IEC 60028 / IEC 60228
Temperature coefficient α₂₀ (Cu / Al) Cu 0.00393 / Al 0.00403 K⁻¹ IEC 60028
Derating by installation method Conduit −15%, trunking −22% (values used here) — Engineering rules of thumb; use IEC 60364-5-52 / GB/T 16895 for design

Note: voltage-drop limits (3% for lighting, 5% for power) and installation derating are engineering conventions; the permissible values must follow the current supply-design code and the project specification.