🚀 Transformer Sizing Calculator

From total load power, power factor and voltage level, computes apparent power and load current, then recommends a standard transformer capacity and loading rate.

📐 计算公式
变压器选型:视在功率 S = P ÷ cosφ(kVA);计算电流 I = S ÷ (√3·U)(A);理论所需容量 = S ÷ (目标负载率%/100),推荐容量取 TX_STD 标准系列(30-10000 kVA)向上最近的档位;实际负载率 = S ÷ 推荐容量 × 100(%);无功功率 Q = P·tan(arccos cosφ)(kvar)。校验:四项须有效且非零,否则报「请输入有效正数(功率、功率因数、电压需大于 0)」。判据:电压 U≤0.4kV 低压配电、≤10 配电变压器、≤35 区域变电、否则主变电所;负载率 <50 偏低(容量浪费)、≤85 合理、≤95 偏高(注意温升)、>95 过高(需扩容)。
由负载总功率 P 与功率因数 cosφ 计算视在功率 S,求计算电流 I,依据目标负载率推荐标准变压器容量并评估实际负载率是否合理。
💡 视在功率 S=P/cosφ;计算电流 I=S/(√3×U);变压器容量按 S/负载率 选取标准容量。

Formula & Standard References

ItemFormulaSource / Standard
Apparent power Apparent S = P ÷ cosφ (kVA); current I = S ÷ (√3·U) (A) Transformer sizing
Capacity Required cap = S ÷ (target load%/100); pick nearest std size up Transformer sizing
Load% / reactive Actual load% = S ÷ rated × 100; reactive Q = P·tan(arccos cosφ) Transformer sizing
⚠️ 注意事项
  • 标准容量(kVA):30/50/63/80/100/125/160/200/250/315/400/500/630/800/1000/1250/1600/2000/2500
  • 最佳负载率 70%~85%,过低浪费投资,过高影响寿命
  • 常用电压等级:0.4kV(低压)、10kV、35kV、110kV
  • 按 Enter 快速计算,Ctrl/Cmd + Enter 复制结果;纯前端运行,数据不上传

🕘 最近计算

暂无计算记录