⚡ Conductor Ampacity Selection
From current, ambient temperature, laying method and line length, selects a conductor cross-section and verifies the voltage drop.
📐 计算公式
单程电阻 R = ρ·L/1000;电压降 ΔU = 2·I·R(来回双线);压降% = ΔU/V × 100%;线损 P = 2·I²·R(W)
导线载流选型:基于电流、环境温度与敷设方式,按导线载流量修正曲线选择线径,校核电压降与温升,用于配电线路设计。
💡 按校正载流量选截面;压降 ΔU=2×I×R×L,铜电阻率 0.0184 Ω·mm²/m
Formula & Standard References
| Item | Formula | Source / Standard |
|---|---|---|
| One-way R | One-way R = ρ × L / 1000 | Voltage drop |
| Drop | Drop ΔU = 2 × I × R (round trip) | Voltage drop |
| Drop% / loss | Drop% = ΔU / V × 100; loss P = 2 × I² × R (W) | Voltage drop |
⚠️ 注意事项
- 压降一般不超过 5%(照明 3%、动力 5%)
- 穿管敷设降容 15%,线槽敷设降容 22%
- 长距离输电需校验压降,可能需放大截面
- 本工具纯前端运行,数据不会上传到服务器
📐 Material Constants
Basis for the resistivity and derating values used here, for verification and citation
| Constant | Value | Unit | Source |
|---|---|---|---|
| Volume resistivity of annealed copper (20 ℃) | 1.7241e-8 (= 0.017241) | Ω·m (Ω·mm²/m) | IEC 60028 (IACS 100%) |
| Volume resistivity of hard-drawn aluminium (20 ℃) | 2.8264e-8 (= 0.028264) | Ω·m (Ω·mm²/m) | IEC 60028 / IEC 60228 |
| Temperature coefficient α₂₀ (Cu / Al) | Cu 0.00393 / Al 0.00403 | K⁻¹ | IEC 60028 |
| Derating by installation method | Conduit −15%, trunking −22% (values used here) | — | Engineering rules of thumb; use IEC 60364-5-52 / GB/T 16895 for design |
Note: voltage-drop limits (3% for lighting, 5% for power) and installation derating are engineering conventions; the permissible values must follow the current supply-design code and the project specification.