选线径别凭感觉:输入负载电流、导线材质与敷设方式,推荐最小安全截面(BV 铜线系列),并对照载流量表给出余量提示。
Wire Gauge Selector: computes and outputs results from the input parameters.
| Item | Formula | Source / Standard |
|---|---|---|
| Loop R | Loop R = ρ × 2L / S (two-wire; ρ resistivity, L length, S gauge) | Wire sizing |
| Drop | Drop ΔU = I × R; drop% = ΔU / 220 × 100% | Wire sizing |
| Upstep | If > 5%, increase wire gauge one step | Wire sizing |
Resistivity and ampacity references used here, for verification and citation
| Constant | Value | Unit | Source |
|---|---|---|---|
| Volume resistivity of annealed copper (20 ℃) | 1.7241e-8 (= 0.017241) | Ω·m (Ω·mm²/m) | IEC 60028 (IACS 100%) |
| Volume resistivity of hard-drawn aluminium (20 ℃) | 2.8264e-8 (= 0.028264) | Ω·m (Ω·mm²/m) | IEC 60028 / IEC 60228 (this page uses 0.0283) |
| Temperature coefficient α₂₀ (Cu / Al) | Cu 0.00393 / Al 0.00403 | K⁻¹ | IEC 60028 |
| Basis for current-carrying capacity | Derating tables by installation method and ambient temperature | — | IEC 60364-5-52 (wiring systems ampacity) |
Note: aluminium conductors carry roughly 75–80% of the copper rating, and conduit installation has lower ampacity than surface wiring; both are empirical engineering rules. Formal design must follow the IEC 60364-5-52 / GB/T 16895 tables and the GB 50303 acceptance code.