Plan fire extinguisher placement for emergency response.
根据保护面积、火灾类型和危险等级,按常用设计参数估算灭火器的配置数量。
请输入参数后计算。
| Item | Formula / Note | Source / Standard |
|---|---|---|
| Coverage area per unit | A = 50 m² (4kg ABC, medium) | GB 50140-2005 §7 |
| Base configuration | ≥3 (severe) / ≥2 (medium) per point | GB 50140-2005 §6 |
| Extinguishing rating | 2A per unit, class A medium | GB 50140-2005 Appendix |
| Travel distance | ≤20 m for class A portable | GB 50140-2005 §5.2 |
| Minimum units | N = A/Qe | GB 50140-2005 §7.3 |
| Wheeled units | Wheeled ≈ 2.5× portable rating | GB 50140 commentary |