Calc Area Lux
Key formulas: Math.ceil(totalFlux÷lampFlux)
| Item | Formula / Note | Source / Standard |
|---|---|---|
| Lumen method | E = Φ × UF × MF ÷ A → total flux Φ = E × A ÷ (UF × MF) | GB 50034-2013 Standard for Lighting Design of Buildings |
| Residential illuminance | Living room 100 lx, bedroom 75 lx (general); 300 lx for reading (mixed lighting) | GB 50034-2013 Table 5.2.1 |
| UF and MF | UF 0.4–0.6 (higher for light rooms); MF 0.8 residential, 0.6–0.7 dirty environments | GB 50034-2013 Chapter 4 |
| LED power density | Residential LPD target ≤5–6 W/m² (current limit 6–7 W/m²) | GB 51348-2019 Standard for Design of Electrical Installation in Civil Buildings |
基于流明法(平均照度法)计算房间所需灯具数量与总功率,内置多种灯具光效与典型照度标准,辅助照明设计与节能校核。